Conductivity/TDS Control with Choice of Bleed Programs
Temperature Monitoring
Make Up and Bleed Watermeter Totalizers
Langelier Saturation Index for Water Balance
Six Feed Programs for 4 Chemical Additives
“Booster” Chemical Feed to Schedule a Delayed One Time Feed Event
Time Based Low Chemical Level Alarm
Probe Failure Indication and Alarm
Automatic Probe Rinse to Clean Sensors
Integral Data Logging for up to 999 Points with RS232 Communications
NEMA 4X Wall Mount Enclosure
Water Test for Alkalinity and Hardness
Remote Computer Operation with Windows Software
Quick Release Enclosure Design for Fast Access and Wiring
产品描述
The CDCN13 Series has been discontinued. Please see the PHUCN600 Series as a possible alternative or contact our Flow Engineering Department.
The CDCN13 is a fully programmable controller designed for
complete chemical automation (conductivity, pH and ORP) as well
as control of chemical additives, all with data logging, RS232
communications, and available RS485. This controller can easily
handle cooling tower, boiler, industrial process water, food
processing, drinking water and wastewater treatment applications.
Featuring high accuracy and easy installation and operation,
engineering units can be displayed in either US or metric values
using the 16-button keypad and the large, 8-line LCD readout with
simple scroll-through menus. Standard features include
conductivity control, with the ability to control 4 additive feed
programs. You can get a readout of the probe temperature. pH and
ORP measurement and control is available, as is a safety flow
switch contact, and RS485 communications.
The CDCN13 has 8 control relay outputs, for up to 4 chemical
additives, fill valve, bleed valve, probe rinse, and remote alarm.
Standard features also include dynamic probe failure testing for
pH/ORP sensors, allowing the controller to detect a probe failure
quickly after it occurs, so the user can avoid dangerous out-ofrange
conditions. The automatic probe rinse can be used for either
manual or automatic cleaning of pH or ORP electrodes.
SPECIFICATIONS Measurement Range: Conductivity: 0 to 20000 µS/cm or ppm; conversion factor for TDS pH: 0 to 14 pH; setpoint for acid or base feed ORP: 0 to 999 mV; programmable shock treatment Accuracy: Conductivity: ±1% rdg pH: ±0.1 pH ORP: ±10 mV Resolution: Conductivity: 1µS pH: 0.01 pH ORP: 1 mV Temperature Range: -18 to 60°C (0 to 140°F) Watermeter Input: For totalizer function Sensor Calibration: 1, 2 or 3 points Control Modes: Off, manual, auto, timer, bleed and feed, bleed-then-feed, daily schedule Langelier Index: Water balance display calculated from pH, temp, total alkalinity and calcium hardness Alarms: High/Low, out-of-range, overfeed and total run time; visual, audible and external (5 A) alarms Data Logging: On-board memory for 999 tests; RS232 communication port for local download and printing Networking: RS485 port for multiple connections (optional) Remote Operation: Software and graphical display for Windows Power: 115/230 Vac, 10 A Control Outputs: 5 A relays, SPST; 4 chemical additive, one each: bleed, fill, probe rinse and alarm Probe Sensor Failure: For pH or ORP electrode Mechanical: NEMA 4X enclosure Display: Eight line LCD; 16-button keypad Dimensions: 336 x 285 x 167 mm (13.21 x 11.21 x 6.59") Shipping Weight: 8.2 kg (18 lb)
† 所有金额以RMB显示 注: Comes complete with operator's manual and 3V lithium battery.
Probes sold separately.
When ordering the conductivty or pH controller, it is recommended to purchase pH buffer solution.
订购示例: (1) CDSA-1413 conductivity standard solution, 1413 µS/cm, ¥363.22