Heavy Duty Electropneumatic Converters I/P and E/P Models |
IP510, EP510, IP511, EP511 Series |
|
|
|
|
Heavy Duty Electropneumatic Converters
|
Click for larger image. |
|
|
¥
8,980.00
IP511-X27
|
|
Hazardous Locations and Intrinsically Safe Ratings
|
|
NEMA 4X (IP65)
|
|
0.1% Accuracy Typical
|
|
Closed Loop Pressure Feedback Control
|
|
Built-in Volume Booster Provides Flow Up to 12 SCFM
|
|
Easy Access to Zero and Span
|
|
Damping Pot Prevents Overshoot and Hunting
|
|
Low Air Consumption
|
|
Mount at Any Angle
|
|
Compact and Lightweight
|
|
Virtually No Sensitivity to Supply Pressure Changes
|
|
Removable Orifice for Easy Maintenance
|
|
Buna-N Seals Standard, Fluorocarbon Optional
|
View related products - Valves, Regulators and I/P Converters
|
| |
|
|
|
The IP510/EP510 Series are a patented family of electro-pneumatic
instruments that are used to reduce a pneumatic supply pressure to a
regulated output pressure which is directly proportional to a
two-wire current or three-wire voltage input. This design incorporates
closed loop sensing of the output pressure to achieve excellent
accuracy and vibration stability. They also feature a unique damping
circuit which can be adjusted to prevent overshoot and actuator
hunting. Model selection includes General purpose NEMA 1, and
Water-tight/Corrosion Resistant NEMA 4X (IP65). All models carry
Hazardous Locations and intrinsically safe ratings.
SPECIFICATIONS
Accuracy:
Typical: ±0.1% of output span
Max: ±0.25% of output span
Hysteresis:
Typical: ±0.01% of output span
Max: ±0.10% of output span
Deadband: No effect
Repeatability:
Typical: ±0.01% of output span
Max: ±0.10% of output span
Ambient Temperature Effect Zero:
Typical: ±0.004% of nominal span/°F
Max: ±0.022% of nominal span/°F
Ambient Temperature Effect Span:
Typical: 0.013% of calibrated span/°F
Max: 0.022% of calibrated span/°F
Temperature Effect: ≤0.02%/°F, zero and span effects combined
Operating Temperature Range:
Buna-N Elastomers: -29 to 71°C (-20 to 160°F)
Fluorocarbon Elastomers: -18 to 71°C (0 to 160°F)
Storage Temperature Range:
Buna-N Elastomers: -40 to 93°C (-40 to 200°F)
Fluorocarbon Elastomers: -26 to 93°C (-15 to 200°F)
Vibration Effects: Less than 0.5% of span per 1 g, 5 to 2000 Hz, 3 g max, 3 axes
Mounting Position Effect: Not measurable
Loop Load, I/P Transducer:
Less than 10 Vdc drop at 20 mA
Less than 12 Vdc drop at 50 mA
Supply Voltage, E/P Transducer:
Intrinsically Safe/Non-Incendive: 9 to 28 Vdc, less than 20 mA
General Purpose: 9 to 40 Vdc, less than 20 mA
Supply Voltage Effect: No effect
Signal Impedance E/P Transducer: 6000 Ω minimum
RFI/EMI Effect NEMA 4X (IP66): Less than 0.25% of span change in output 10 V/meter, 20 to 1000 MHz (Reference SAMA PML 33.1 to 1978, 2 to abc)
Supply Pressure Sensitivity: No effect
Effective Air Consumption: 0.07 SCFM (2 LPM) maximum
Supply Pressure: 100 psig (6.9 bar) maximum*
* For models with zero output capability maximum supply pressure = 40 psi (2.8 bar) above maximum output, except for 0 to 100 and 0 to 120 psi models that have a maximum supply pressure of 130 psi (9 bar) and 140 psi (9.7 bar) respectively.
Dimensions
IP510: 102 H x 48 W x 89 mm D (4.01 x 1.88 x 3.5")
IP511: 144 H x 112 mm W (5.66 x 4.36")
Port Sizes:
Pneumatic: ¼ FNPT
Electrical: ½ FNPT
|
|
|
|
|
|
† Price are shown in RMB.
Ordering Example: (1) IP511-X15 current to pressure converter with 4-20 mA input, 3-15 psi output and NEMA-4X enclosure, ¥8,980.00
|
|
|
|
|
|
|
|
|
Part Number Builder |
|
|
|
|
|
|
Option Descriptions
|
(1)
|
Enclosure Type
|
|
Select IP510 for NEMA 1 (IP00) Enclosure with 4 to 20 mA input IP511 for NEMA 4X (IP66) Enclosure with 4 to 20 mA input EP510 for NEMA 1 (IP00) Enclosure with 1 to 5 Vdc input EP511 for NEMA 4X (IP66) Enclosure with 1 to 5 Vdc input
(2)
|
Specify Output Range
|
|
Select X15 for 3 to 15 psig X27 for 3 to 27 psig X30 for 6 to 30 psig 060 for 0 to 60 psig 0120 for 0 to 120 psig
(3)
|
Seal Material
|
|
Select Nothing(leave field blank) for Buna-N seals (standard) -F for Fluorocarbon seals
|
NOTE: All combinations may not be valid, check spec sheet for valid part numbers.
|
| |
|
|
|
|
|
| |
|
Back to top
|
|
|